Function 16: writing n successive words, 5 error messages, Error messages – Rice Lake PR5230 Fieldbus Transmitter User Manual
Page 174: J-bus/modbus protocol, Pr 5230 instrument manual

J-Bus/ModBus Protocol
PR 5230 Instrument Manual
EN-174
Sartorius
Function 16: Writing n Successive Words
Command
Device 
address 
Function 
number 
Address of 
1st word 
Number of 
words 
Number of 
bytes 
Value of 
words 
1 byte
1 byte
2 bytes
2 bytes
1 byte
n bytes
Range
0...127
16
0...63
1...64
2...128
 
 
MSB
LSB
MSB
- - - - - - MSB
LSB
1
st
word
last word
 
Reply 
Device address
Function 
number 
Address of 1st 
word 
Number of 
words 
1 byte
1 byte
2 bytes
2 bytes
If the address is out of the permissible range (0...63), an error message is sent as a reply (the address plus the 
number of bytes must not exceed 64). 
Example of function 16 for writing the limit_1 switch-on point using value 893 with ModBus-RTU: 
Command 
1
16 0
48 0
2
4
0
0
3
125 CRC CRC
Reply
1
16 0
48 0
2
CRC CRC
Example with ModBus-TCP: 
Command 
47 15 0
0
0
8
0
16 0
48 0
2
4
0
0
3
125
Reply
47 15 0
0
0
6
0
16 0
48 0
2
The individual bytes are shown.
6.5
Error Messages
If a command was transmitted correctly, but cannot be executed because e.g. the address is too high, an error 
message is sent as a reply to the command. 
The error message has the following format: 
Device address
Function number +128
Error number
CRC 16
1 byte
1 byte
1 byte
2 bytes
The 2nd byte contains the received function number; the most significant bit is set additionally. 
Meaning of the error number: 
1
The function number is unknown
2
The address is out of the permissible range
3
The data format is faulty (e.g. more data than specified in the number were written)