Analog output, Er 5.10, Commissioning – Rice Lake PR5230 Fieldbus Transmitter User Manual
Page 158: Pr 5230 instrument manual, 10 analog output
![background image](/manuals/639397/158/background.png)
Commissioning
PR 5230 Instrument Manual
EN-158
Sartorius
5.10
Analog Output
The analog output card PR 5230/06 can be mounted in slot 1.
Define the analog output parameters under
-[Analog output
parameter
].
Press
to select the specific parameter.
Press
to select the respective values.
Setup/
Analog output parameter
Analog mode
Gross
D08
Analog range
0…20 mA
Output on error
0 mA
Output if < 0
linear
Output if > Max
linear
Weight at 0/4 mA
0 g
Weight at 20 mA
240000 g
[Analog mode]
[no output]
The analog output is not used
[Gross
D08]
Output of the gross weight
[Net if tared D09]
Output of the net weight, if tared; otherwise gross weight
[Selected
D11]
Output Gross or Net, depending on SPM-Bit X72
[Transparent D30]
Output of the value in D30
[Analog range]
[0...20 mA]
Output of 0... 20 mA
[4...20 mA]
Output of 4... 20 mA
[Output on error]
[0 mA]
Set the output to 0 mA
[4 mA]
Set the output to 4 mA
[20 mA]
Set the output to 20 mA
[Output if < 0]
[0 mA]
Set the output to 0 mA
[4 mA]
Set the output to 4 mA
[20 mA]
Set the output to 20 mA
[linear]
The output drops below 4 mA up to the limitation
(at 4 .. 20 mA)
[Output if > Max] [0 mA]
Set the output to 0 mA
[4 mA]
Set the output to 4 mA
[20 mA]
Set the output to 20 mA
[linear]
The output exceeds 20 mA up to the limitation
[Weight at 0/4 mA]
Weight value for 0/4 mA output
[Weight at 20 mA]
Weight value for 20 mA output
Press
to return to the previous menu.