beautypg.com

5 network port, 6 optocoupler inputs, Network port – Rice Lake PR5230 Fieldbus Transmitter User Manual

Page 43: Optocoupler inputs

background image

PR 5230 Instrument Manual

Installing the Instrument and Plug-in Cards

Sartorius

EN-43

4.2.5

Network Port

The network port is built in as standard equipment. The port contains powerful TCP/IP connection circuitry
with transfer rates of 10 or 100 Mbit/sec. Function checking is possible via the LED to the right of the
display (act) or via the LED in the RJ 45 socket when the housing is open.

Transfer rate

10 Mbit/sec, 100 Mbit/sec,
full/half duplex, auto-detection

Connection method Point to point
Cable

Pre-fabricated cable with M20 cable
gland

Cable impedance

150 ¥

Electrical isolation

Yes

Cable length

Max. 7 m

Connection

RJ-45 socket inside the housing

Remote operation of the PR 5230 from the Notebook/PC is
possible; install VNC program Release 3.3.7* on the
Notebook/PC. For setting the network address, see
Chapter 5.3.3.
* Sartorius guarantees the functionality only if this version is

used!

4.2.6

Optocoupler Inputs

The main board has 3 digital inputs for process control, electrically isolated by optocouplers, each bipolar
potential-free.

Number of inputs

3 (CH 1, CH 2, CH 3 )

Input signal

Logic 0: 0 ... 5 V DC or open
Logic 1: 10 ... 28 V DC
Internal 12 V DC supply or
external supply required.

Input current

<11 mA @ 24 V
< 5 mA @ 12 V
Protected against incorrect polarity.

Electrical isolation

Via optocoupler,
internal supply is potential-free.

Connection

Plug-in 6-pin screw terminal block,
conductor cross-section max. 1.5 mm²

Cable

Shielded, max. 50 m.
The cable screen must be connected in
the sleeve of the cable gland!