5 network port, 6 optocoupler inputs, Network port – Rice Lake PR5230 Fieldbus Transmitter User Manual
Page 43: Optocoupler inputs
PR 5230 Instrument Manual
Installing the Instrument and Plug-in Cards
Sartorius
EN-43
4.2.5
Network Port
The network port is built in as standard equipment. The port contains powerful TCP/IP connection circuitry
with transfer rates of 10 or 100 Mbit/sec. Function checking is possible via the LED to the right of the
display (act) or via the LED in the RJ 45 socket when the housing is open.
Transfer rate
10 Mbit/sec, 100 Mbit/sec,
full/half duplex, auto-detection
Connection method Point to point
Cable
Pre-fabricated cable with M20 cable
gland
Cable impedance
150 ¥
Electrical isolation
Yes
Cable length
Max. 7 m
Connection
RJ-45 socket inside the housing
Remote operation of the PR 5230 from the Notebook/PC is
possible; install VNC program Release 3.3.7* on the
Notebook/PC. For setting the network address, see
Chapter 5.3.3.
* Sartorius guarantees the functionality only if this version is
used!
4.2.6
Optocoupler Inputs
The main board has 3 digital inputs for process control, electrically isolated by optocouplers, each bipolar
potential-free.
Number of inputs
3 (CH 1, CH 2, CH 3 )
Input signal
Logic 0: 0 ... 5 V DC or open
Logic 1: 10 ... 28 V DC
Internal 12 V DC supply or
external supply required.
Input current
<11 mA @ 24 V
< 5 mA @ 12 V
Protected against incorrect polarity.
Electrical isolation
Via optocoupler,
internal supply is potential-free.
Connection
Plug-in 6-pin screw terminal block,
conductor cross-section max. 1.5 mm²
Cable
Shielded, max. 50 m.
The cable screen must be connected in
the sleeve of the cable gland!