Integrating Fieldbus into Rockwell Automation Logix System 2-33
Fieldbus Alarm Conditions
Fieldbus devices provide both process and device related alarms. The
fieldbus devices themselves own their alarm data; generates and clears
the alarms and events. The process alarms are associated with process
variable conditions and they are reported as process alarms into
ProcessLogix.
The device alarms are associated with actual device conditions or
processes within the block as indicated by BLOCK_ERR and
XD_ERROR bitstring alarms. These alarms are reported as device or
system alarms into the ProcessLogix notification system. Table 2.K
summarizes the possible fieldbus alarm enumerations and lists the
alarm/event type identification to be used in the alarm summary and
event summary displays in Station.
TIP
Fieldbus alarm functions do not support rate of
change (ROC) alarms. ROC alarms can only be
generated in applications that use ProcessLogix data
acquisition blocks for input signal conditioning.
Table 2.K Fieldbus alarm enumerations and alarm/event type identification
Enumeration
Description
Alarm/Event Type
UNDEF
Undefended Alarm
No Action
LO
Low Limit Alarm
PVLO
HI
High Limit Alarm
PVHI
LO LO
Critical Low Limit Alarm
PVLOLO
HI HI
Critical High Limit Alarm
PVHIHI
DV LO
Deviation Low Alarm
DEVLO
DV HI
Deviation High Alarm
DEVHI
DISC
Standard Discrete Alarm
OFFNORM
DISC
Standard Discrete Alarm
CHNGOFST
DISC
DevCtl Fail Alarm
FBDCFAIL
DISC
DevCtl Accept Alarm
FBDCACC
DISC
DevCtl Ignore Alarm
FBDCIGN
BLOCK
BLOCK_ERR: 0 (Other (LSB)
FFOTHER
BLOCK
BLOCK_ERR: 1 (Block Configuration Error)
FFBLKCFG
BLOCK
BLOCK_ERR: 2 (Link Configuration Error)
FFLNKCFG
BLOCK
BLOCK_ERR: 3 (Simulate Active)
FFSIMACT
BLOCK
BLOCK_ERR: 4 (Local Override)
FFLO