Table a.81 out_d table a.82 out_hi_lim – Rockwell Automation PLC-5 Fieldbus Solutions for Integrated Architecture User Manual User Manual
Page 210
Publication 1757-UM006A-EN-P - May 2002
A-30 Standard Function Block Parameters
Table A.81 OUT_D
Table A.82 OUT_HI_LIM
Valid Views
VIEW_1, VIEW_3
Storage
Non-Volatile
Remarks
Normally, the operator has permission to write this value, but PROGRAM or
LOCAL remove that permission and grant it to a supervisory computer or a
local control panel.
The Data type consists of the value and status of floating point parameters
that are Inputs or Outputs. It uses the following two elements.
• Status
• Value
Classification
Record
Description
Represents the primary discrete value calculated as a result of executing the
function.
FF Data Type
DS-66
Range
OUT_STATE
Usage
O/Primary Output
Length
2
Valid Views
VIEW_1, VIEW_3
Storage
Non-Volatile
Remarks
Normally, the operator has permission to write this value, but PROGRAM or
LOCAL remove that permission and grant it to a supervisory computer or a
local control panel.
The data type consists of the value and status of discrete value parameters. It
uses the following two elements.
• Status
• Value
Classification
Simple Variable
Description
Defines the maximum output value limit in all modes, unless the
CONTROL_OPTS selection No Out limits in Manual is chosen.
FF Data Type
Float
Range
OUT_SCALE +/- 10 percent
Usage
C/Contained
Length
4
Valid Views
VIEW_2
Storage
Static
Remarks
Initial value is 100.