A-38 Standard Function Block Parameters
Table A.102 ROUT_OUT
Table A.103 RS_STATE
Valid Views
VIEW_3
Storage
Dynamic
Remarks
The data type consists of the value and status of floating point parameters
that are Inputs or Outputs. It uses the following two elements.
• Status
• Value
Classification
Record
Description
Represents block output and status. It serves as input to a host for back calcu-
lation in ROut mode that allows action to be taken under limited conditions or
mode change
FF Data Type
DS-65
Usage
C/Remote-Output Out
Length
5
Valid Views
VIEW_3
Storage
Dynamic
Remarks
Read Only
The data type consists of the value and status of floating point parameters
that are Inputs or Outputs. It uses the following two elements.
• Status
• Value
Classification
Simple Variable
Description
Defines the state of the function block application state machine.
FF Data Type
Unsigned 8
Range
1: Start/Restart
2: Initialization
3: On-Line Linking
4: On-Line
5: Standby
6: Failure
Usage
C/Resource State
Length
1
Valid Views
VIEW_1, VIEW_3
Storage
Dynamic
Remarks
Read Only