Cxxx blocks – Rockwell Automation PLC-5 Fieldbus Solutions for Integrated Architecture User Manual User Manual
Page 187

Publication 1757-UM006A-EN-P - May 2002
Standard Function Block Parameters A-7
Cxxx Blocks
Table A.17 CAS_IN
Table A.18 CAS_IN_D
Table A.19 CHANNEL
Valid Views
VIEW_2
Storage
Static
Remarks
Initial value is 0.
Classification
Record
Description
Represents the remote setpoint value that must come from another fieldbus
block or a distributed control system (DCS) block through a defined link.
FF Data Type
DS-65
Usage
I/Cascade Input
Length
5
Valid Views
VIEW_1, VIEW_3
Storage
Dynamic
Remarks
The data type consists of the value and status of floating point parameters
that are Inputs or Outputs. It uses the following two elements.
• Status
• Value
Classification
Record
Description
Represents the remote setpoint value for a discrete block that must come from
another fieldbus block or a distributed control system (DCS) block through a
defined link.
FF Data Type
DS-66
Usage
I/Cascade Input
Length
2
Valid Views
VIEW_1, VIEW_3
Storage
Dynamic
Remarks
The data type consists of the value and status of discrete value parameters. It
uses the following two elements.
• Status
• Value
Classification
Simple Variable
Description
The number of the logical hardware channel that is connected to this I/O
block. It defines the transducer used to connect to the physical world.
FF Data Type
Unsigned 16
Range
1 to Manufacturer Limit