Vxxx blocks, Wxxx blocks – Rockwell Automation PLC-5 Fieldbus Solutions for Integrated Architecture User Manual User Manual
Page 229

Publication 1757-UM006A-EN-P - May 2002
Standard Function Block Parameters A-49
Vxxx Blocks
No V parameters
Wxxx Blocks
Table A.130 WRITE_ALM
Table A.131 WRITE_LOCK
Table A.132 WRITE_PRI
Classification
Record
Description
Represents alert that is generated if the write lock is cleared.
FF Data Type
DS-72
Usage
C/Alarm
Length
1, 3
Storage
Dynamic
Remarks
Read Only
The data type describes discrete alarms using the following five elements:
• Unacknowledged
• Alarm State
• Time Stamp
• Subcode
• Value
Classification
Simple Variable
Description
Used to disallow writes from anywhere, except to unlock/clear this parameter,
when it is locked/set. Inputs will continue to read.
FF Data Type
Unsigned 8
Range
1: Unlocked
2: Locked
Usage
C/Contained
Length
1
Valid Views
VIEW_2
Storage
Static
Remarks
The operator can control PROGRAM and LOCAL access to this value.
Classification
Simple Variable
Description
Defines the priority of the alarm generated by clearing the WRITE_LOCK.
FF Data Type
Unsigned 8
Range
0 to 63
Usage
C/Alert Priority