Standard Function Block Parameters A-37
Table A.99 RESET
Table A.100 RESTART
Table A.101 ROUT_IN
Classification
Simple Variable
Description
Represents the Integral time constant in seconds. It is the inverse of repeats
per minute.
FF Data Type
Float
Range
Positive
Usage
C/Contained
Length
4
Valid Views
VIEW_4
Storage
Static
Classification
Simple Variable
Description
Allows a manual restart to be initiated. The following degrees of restart are
possible.
• Run
• Restart Resource
• Restart with Defaults
• Restart Processor
FF Data Type
Unsigned 8
Range
1: Run
2: Restart Resource
3: Restart with Defaults
4: Restart Processor
Usage
C/Contained
Length
1
Storage
Dynamic
Remarks
Changing this parameter, may be fatal to communication.
Classification
Record
Description
Represents target output and status provided by a host to a control block for
use as the block's output in ROUT mode.
FF Data Type
DS-65
Usage
C/Remote-Output In
Length