Standard Function Block Parameters A-3
Table A.6 BIAS
Table A.7 BKCAL_HYS
Table A.8 BKCAL_IN
Valid Views
VIEW_4
Storage
Static
Remarks
Initial value is 0
Classification
Simple Variable
Description
Specifies the Bias value in engineering units to be used in computing the
function block output
FF Data Type
Float
Range
OUT_SCALE +/- 10 percent
Usage
C/Contained
Length
4
Valid Views
VIEW_1, VIEW_3
Storage
Non-Volatile
Remarks
Normally, the operator has permission to write these values, but PROGRAM or
LOCAL remove the permission and grant it to a supervisory computer or a local
control panel.
Classification
Simple Variable
Description
Defines the amount of change an output value must attain from the limit
before the limit status is turned OFF.
FF Data Type
Float
Range
0 to 50 percent of output span
Usage
C/Contained
Length
4
Valid Views
VIEW_4
Storage
Static
Remarks
Initial value is 0.5 percent
Classification
Record
Description
The value and status from a lower block's BKCAL_OUT that is used to prevent
reset windup and to initialize the control loop.
FF Data Type
DS-65
Usage
I/Back-Calculation Input
Length
5