Table a.23, Table a.24 cycle_sel, Control_opts bit selections – Rockwell Automation PLC-5 Fieldbus Solutions for Integrated Architecture User Manual User Manual
Page 189
Publication 1757-UM006A-EN-P - May 2002
Standard Function Block Parameters A-9
Table A.23
CONTROL_OPTS Bit Selections
Table A.24 CYCLE_SEL
Valid Views
VIEW_4
Storage
Static
Remarks
See the following for a list of the control options by bit and applicable function
block.
Bit
Meaning
Function Block
BG
CS
ML
PD
PID
RA
0
Bypass Enable (LSB)
X
X
1
SP-PV Track in Man
X
X
X
2
SP-PV Track in ROut
X
X
3
SP-PV Track in LO or IMan
X
X
X
4
SP Track retained target
X
X
X
X
5
Direct Acting
X
X
6
Balance Ramp
X
X
X
7
Track Enable
X
X
X
X
X
8
Track in Manual
X
X
X
X
X
9
Use PV for BKCAL_OUT
X
X
X
10
Act on IR
X
X
X
11
Use percent for IN_1
X
X
12
Obey SP limits if Cas or RCas
X
X
X
X
13
No OUT limits in Manual
X
X
X
X
X
X
14
Reserved
15
Reserved
Classification
Simple Variable
Description
A bit string to identify the block execution method selected for this resource.
FF Data Type
Bit String
Usage
C/Contained
Length
2
Valid Views
VIEW_2
Storage
Static
Remarks
Changing this parameter may be fatal to communication.