Notification scheme, Fieldbus versus processlogix alarm priorities, Notification scheme -32 – Rockwell Automation PLC-5 Fieldbus Solutions for Integrated Architecture User Manual User Manual
Page 76: Fieldbus versus processlogix alarm priorities -32
Publication 1757-UM006A-EN-P - May 2002
2-32 Integrating Fieldbus into Rockwell Automation Logix System
Notification Scheme
Fieldbus versus ProcessLogix Alarm Priorities
The Fieldbus alarms are closely integrated with the existing
ProcessLogix notification system. The ProcessLogix Server handles
FIM alarms in the same way it handles Control Processor ones. But,
the fieldbus devices themselves own their alarm data and generate the
alarms, clears, and events.
Fieldbus devices use 0 to 15 as numeric priorities for alarm reporting.
ProcessLogix alarms use Journal, Low, High and Urgent as priorities
with a sub-priority of 0 to 255. Table 2.J shows how fieldbus priorities
are mapped to ProcessLogix priorities and severities.
Table 2.J Mapping Fieldbus Priorities to ProcessLogix
Fieldbus Alarm Priority
ProcessLogix Alarm
Priority
ProcessLogix Alarm
Severity
0
(Can never be seen by FIM
or above)
(Can never be seen by FIM
or above)
1
(Can never be seen by FIM
or above)
(Can never be seen by FIM
or above)
2
BLOCK_ERR bit 14
(power-up)
BLOCK_ERR bit 15
(Out-of-Service)
Journal
(Event System Only)
2
3
All other bitstring
indications:
(BLOCK_ERR bits 0-13,
XD_ERROR bits 16-25)
System Level Diagnostic
(High)
2
2 (User selected)
Journal
2
3
Low
3
4
Low
4
5
Low
5
6
Low
6
7
Low
7
8
High
8
9
High
9
10
High
10
11
High
11
12
Urgent
12
13
Urgent
13
14
Urgent
14
15
Urgent
15