Fieldbus status indications, Fieldbus status indications -18 – Rockwell Automation PLC-5 Fieldbus Solutions for Integrated Architecture User Manual User Manual
Page 62

Publication 1757-UM006A-EN-P - May 2002
2-18 Integrating Fieldbus into Rockwell Automation Logix System
The status byte structure consists of a 2-bit quality, most significant bit,
field; a 4-bit substatus field; and a 2-bit limits, least significant bit,
field. The following table provides a breakdown of bit assignments for
general reference. The value of the quality field determines the
applicable substatus field indication.
Fieldbus Status Indications
See Appendix B for list of possible display indications associated with
a given fieldbus status.
Table 2.B Breakdoun of bit assignments
Bit
Quality
Substatus, if Quality field is
Limits
BAD
UNCERTAIN
GOOD
(Non-Cascade)
(1)
GOOD (Cascade)
0
BAD Data Quality
Non-Specific
Non-Specific
Non-Specific
Non-Specific
No Limits
1
UNCERTAIN Data
Quality
Configuration Error
Last Usable Value
Active Block Alarm
Initialization
Acknow-ledge (IA)
Low Limit
2
GOOD
(Non-Cascade)
Data Quality
Not Connected
Substitute
Active Advisory
Alarm
Initialization Request
(IR)
High Limit
3
GOOD (Cascade)
Data Quality
Device Failure
Initial Value
Active Critical
Alarm
Not Invited (NI)
Constant
4
Sensor Failure
Sensor Conversion
Not Accurate
Unacknow-ledged
Block Alarm
Not Selected (NS)
5
No Communication, with
Last Usable Value
Engineering Unit
Range Violation
Unacknow-ledged
Advisory Alarm
Do Not Select (DNS)
6
No Communication, with
no Last Usable Value
Sub-Normal
Unacknow-leged
Critical Alarm
Local Override (LO)
7
Out-Of-Service
Fault-State Active (FSA)
8
Initiate Fault-State (IFS)
(1)
The Good (non-cascade) substatus is used by output connections for fieldbus blocks such as Analog Input and Discrete Input. The Good (cascade) substatus is used by
output connections for fieldbus blocks such as PID. Both of these substatuses are converted to the single ProcessLogix data quality of Good.