beautypg.com

Rockwell Automation PLC-5 Fieldbus Solutions for Integrated Architecture User Manual User Manual

Page 264

background image

Publication 1757-UM006A-EN-P May 2002

F-16 1788-CN2FF Installation Example

5. Select the file with the extension .ffo and click Open.

You see:

6. Click OK to import the DD.

You will receive a message telling you the copy succeeded.

7. Repeat the process to import the DDs for all the other

Foundation Fieldbus devices attached to the 1788-CN2FF.

8. When you have copied all the DDs, click OK again to close the

DD Info window.

9. Click OK to close the Interface Config utility.

TIP

If you get a message that says: Can Not Import
that DD
, there is a good chance that the DD has
already been installed on your system. Go on,
and don't worry for now.

IMPORTANT

You must have a DD for every device or you will not
be able to configure that device.

TIP

If you have just installed the 1788-FFCT software,
you will be asked if you want to restart your
computer now.