A-18 Standard Function Block Parameters
Table A.48 FREE_TIME
Table A.49 FSAFE_TIME
Table A.50 FSAFE_VAL
Classification
Simple Variable
Description
Identifies the percent of block processing time that is free to process addi-
tional blocks.
FF Data Type
Float
Range
0 - 100 percent
Usage
C/Contained
Length
4
Valid Views
VIEW_1, VIEW_3
Storage
Dynamic
Remarks
Read Only
Classification
Simple Variable
Description
Represents the reaction time in seconds from the detection of a failure at the
output block remote setpoint to the output block action, if the condition still
exists.
FF Data Type
Float
Range
Positive
Usage
C/Contained
Length
4
Valid Views
VIEW_4
Storage
Static
Classification
Simple Variable
Description
Defines the preset analog setpoint to use when a failure occurs. Value is
ignored, if the IO_OPTS Failsafe to value option is false.
FF Data Type
Float
Range
PV_SCALE +/- 10 percent
Usage
C/Contained
Length
4
Valid Views
VIEW_4
Storage
Static