Standard Function Block Parameters
(1)
Axxx Blocks
Table A.1 ACK_OPTION
Table A.2 ALARM_HYS
(1)
This reference information is provided by
F
OUNDATION
™ Fieldbus.
Want more Foundation Fieldbus information?
Visit the Fieldbus Foundation web site at www.fieldbus.org, or the
following address, for more information:
9390 Research Blvd.
Suite II-250
Austin, TX 78759-9780
Classification
Simple Variable
Description
Selects whether alarms associated with the block will be automatically
acknowledged.
FF Data Type
Bit String
Range
1: Unacknowledge
Usage
C/Contained
Length
2
Valid Views
VIEW_4
Storage
Static
Remarks
Initial value is 0
Classification
Simple Variable
Description
Defines the amount of change a PV value must attain within the alarm limits
before the alarm condition clears.
FF Data Type
Float
Range
0 to 50 percent of PV span
Usage
C/Contained
Length
4
Valid Views
VIEW_4
Storage
Static
Remarks
Initial value is 0.5 percent