Rockwell Automation PLC-5 Fieldbus Solutions for Integrated Architecture User Manual User Manual
Page 211
![background image](/manuals/579476/211/background.png)
Publication 1757-UM006A-EN-P - May 2002
Standard Function Block Parameters A-31
Table A.83 OUT_LO_LIM
Table A.84 OUT_SCALE
Table A.85 OUT_STATE
Classification
Simple Variable
Description
Defines the minimum output value limit in all modes, unless the
CONTROL_OPTS selection No Out limits in Manual is chosen.
FF Data Type
Float
Range
OUT_SCALE +/- 10 percent
Usage
C/Contained
Length
4
Valid Views
VIEW_2
Storage
Static
Remarks
Initial value is 0.
Classification
Record
Description
Defines the high and low scale values, engineering units code, and number of
digits to the right of the decimal point to be used in displaying the OUT param-
eter and parameters that have the same scaling as OUT.
FF Data Type
DS-68
Usage
C/Scaling
Length
11
Valid Views
VIEW_2
Storage
Static
Remarks
The Data type consists of data that describes floating point values for display
purposes. It uses the following four elements.
• Engineering Units at 100 percent
• Engineering Units at 0 percent
• Units Index
• Decimal Point
Classification
Simple Variable
Description
Represents the index to the text describing the states of a discrete output.
FF Data Type
Unsigned 16
Usage
C/Contained
Length
2
Valid Views
VIEW_2
Storage
Static