Rockwell Automation Publication 20P-UM001K-EN-P - July 2014
77
Installation and Wiring
Chapter 1
DIP Switch S4 Settings
DIP switch S4 must be configured to be greater than or equal to the maximum
DC input voltage. Maximum DC Input Voltage = (Tach Volts/1000 rpm) x Par
45 [Max Ref Speed] x 1.1. See Drive Reference and Feedback Scaling on page
for details on programming speed feedback values.
Figure 56 - DC Analog Tachometer DIP Switch S4 Example
Table 28 - DC Analog Tachometer DIP Switch S4 Configuration
DIP Switch S15 Settings
DIP Switch S15 is configured for the appropriate drive size at the factory. Do not
change the settings unless you are installing a replacement control board.
Figure 57 - Drive Size DIP Switch S15 Example
ATTENTION: The drive can overspeed if DIP switch S4 is set incorrectly or the
tachometer is wired incorrectly. Failure to observe this precaution could result in
damage to, or destruction of, the equipment.
Maximum DC
Input Voltage
S4-1
S4-8
S4-2
S4-7
S4-3
S4-6
S4-4
S4-5
22V
ON
ON
ON
ON
45V
ON
ON
ON
OFF
90V
ON
ON
OFF
OFF
180V
ON
OFF
OFF
OFF
300V
OFF
OFF
OFF
OFF