Rockwell Automation 23P PowerFlex Digital DC Drive User Manual
Page 185
Rockwell Automation Publication 20P-UM001K-EN-P - July 2014
185
Programming and Parameters
Chapter 3
U
TIL
IT
Y
U
ser D
efine
d
503
504
505
506
507
508
509
510
511
512
513
514
515
516
517
518
[UserDefined0]
[UserDefined1]
[UserDefined2]
[UserDefined3]
[UserDefined4]
[UserDefined5]
[UserDefined6]
[UserDefined7]
[UserDefined8]
[UserDefined9]
[UserDefined10]
[UserDefined11]
[UserDefined12]
[UserDefined13]
[UserDefined14]
[UserDefined15]
General use signed 16 bit variables used for data exchange.
Note: Pars 503…506 can be assigned to analog inputs. The values of Pars 503,
504, and 507…509 can be assigned to an analog output.
Default:
Min/Max:
0
–32768/+32767
16-bit
Int
519
[UsrDefBitWrdA]
A bitmap of Pars 520 [UsrDefBitWrdA0] through 535 [UsrDefBitWrdA15]. With a
parameter it is possible to read or write all of the bits inside a word.
Example:
[UsrDefBitWrdA0]
0
[UsrDefBitWrdA1]
1 = 2
1
=2
[UsrDefBitWrdA2]
0
[UsrDefBitWrdA3]
0
[UsrDefBitWrdA4]
0
[UsrDefBitWrdA5]
1 = 2
5
= 32
[UsrDefBitWrdA6]
1 = 2
6
= 64
[UsrDefBitWrdA7]
0
[UsrDefBitWrdA8]
0
[UsrDefBitWrdA9]
0
[UsrDefBitWrdA10]
1 = 2
10
= 1024
[UsrDefBitWrdA11]
0
[UsrDefBitWrdA12]
1 = 2
12
= 4096
[UsrDefBitWrdA13]
0
[UsrDefBitWrdA14]
0
[UsrDefBitWrdA15]
0
[UsrDefBitWrdA] = 2 + 32 + 64 + 1024 + 4096 = 5218
Notes: The value of digital inputs 1…12 can be written to any of bits 0…7
([UsrDefBitWrdA0]…[UsrDefBitWrdA7]) of this parameter. For example, to assign
digital input 1 to bit 0 of this parameter, select option 37 “UsrDefined0” in
parameter 133 [Digital In1 Sel].
The value of bits 0…7 of this parameter can be written to digital outputs 1…8,
sequentially. In other words, when parameters 145 [Digital Out1 Sel]…152
[Digital Out8 Sel] are assigned option 11 “UserDefinedA”, bit 0 of this parameter is
written to digital output 1, bit 1 is written to digital output 2, bit 2 is written to
digital output 3, etc.
Bits 14 and 15 of this parameter are written to relay outputs 1 and 2, respectively,
when parameters 1392 [Relay Out 1 Sel] and 629 [Relay Out 2 Sel] are assigned
option 11 “UserDefinedA”.
Default:
Min/Max:
0
0 / 65535
16-bit
Int
520 -
535
Fil
e
Gr
oup
No
.
Parameter Name & Description
See
page 114
for symbol descriptions
Values
Da
ta
T
yp
e
Rela
ted
A
A