Set Up the Drive

Adjust parameter settings and enter nameplate data.

Motor Tuning Routines

Run the following three tests in the order listed. Refer to Chapter 2 “Drive Start
Up
” staring on page

91

for details. If these tests have already been performed,

proceed to Torque Prove Setup on page

294

.

Current Tune
This routine measures motor characteristics with the brake set (brake closed).

Verify Motor Rotation and Speed Feedback Polarity
This test checks for correct motor armature and speed feedback device
connections.

Speed Tune
This routine gives better results if the connected equipment allows free motor
rotation. This routine requires the mechanical brake to open and the motor to
run.

If a “TorqPrv Spd Band” fault (F94) occurs during any of the motor tuning
routines, see page

222

for a list of possible errors and actions.

Parameter

Setting

Braking Details

245 [Speed Ramp En]

1 “Enabled”

629 [Relay Out 2]

31 “TP Brake Cmd”

Motor Nameplate Data

175 [Rated Motor Volt]

Motor nameplate voltage

179 [Nom Mtr Arm Amps]

Motor nameplate current

162 [Max Feedback Spd]

Motor nameplate speed

280 [Nom Mtr Fld Amps]

Motor nameplate field current

374 [Drv Fld Brdg Cur]

Drive Field Supply Rating (matching S14)

Motor Control

241 [Spd Trq Mode Sel]

1 “Speed Reg”

Maximum Speed

45 [Max Ref Speed]

Motor nameplate speed

Drive Duty Rating

376 [MtrOvrld Type]

1 “Heavy Duty”

Overload Speed

334 [MtrOvrld Speed]

0% (so no current derating is applied)

Protection

479 [MtrOvrld Flt Cfg]

2 “Fault”

7 [Current limit]

200% (of P179 Nom Mtr Arm Amps)