Rockwell Automation 23P PowerFlex Digital DC Drive User Manual
Page 292
292
Rockwell Automation Publication 20P-UM001K-EN-P - July 2014
Appendix C
Application Notes
Set Up the Drive
Adjust parameter settings and enter nameplate data.
Motor Tuning Routines
Run the following three tests in the order listed. Refer to Chapter 2 “Drive Start
Up” staring on page
for details. If these tests have already been performed,
proceed to Torque Prove Setup on page
.
Current Tune
This routine measures motor characteristics with the brake set (brake closed).
Verify Motor Rotation and Speed Feedback Polarity
This test checks for correct motor armature and speed feedback device
connections.
Speed Tune
This routine gives better results if the connected equipment allows free motor
rotation. This routine requires the mechanical brake to open and the motor to
run.
If a “TorqPrv Spd Band” fault (F94) occurs during any of the motor tuning
routines, see page
for a list of possible errors and actions.
Parameter
Setting
Braking Details
245 [Speed Ramp En]
1 “Enabled”
629 [Relay Out 2]
31 “TP Brake Cmd”
Motor Nameplate Data
175 [Rated Motor Volt]
Motor nameplate voltage
179 [Nom Mtr Arm Amps]
Motor nameplate current
162 [Max Feedback Spd]
Motor nameplate speed
280 [Nom Mtr Fld Amps]
Motor nameplate field current
374 [Drv Fld Brdg Cur]
Drive Field Supply Rating (matching S14)
Motor Control
241 [Spd Trq Mode Sel]
1 “Speed Reg”
Maximum Speed
45 [Max Ref Speed]
Motor nameplate speed
Drive Duty Rating
376 [MtrOvrld Type]
1 “Heavy Duty”
Overload Speed
334 [MtrOvrld Speed]
0% (so no current derating is applied)
Protection
479 [MtrOvrld Flt Cfg]
2 “Fault”
7 [Current limit]
200% (of P179 Nom Mtr Arm Amps)