Example 3: DC Tachometer with Feedback Bypass

This example is similar to example 2 except that it compensates for the loss in
feedback resolution by setting parameter 562 [Anlg Tach Gain].

Par 175 [Rated Motor Volt] = 500V (default)

Par 45 [Max Ref Speed] = 1750 rpm (default)

Set Par 562 [Anlg Tach Gain] = 2.057 (3600/1750)

Par 585 [Overspeed Val] = 1925 rpm (default)

Set DIP switch S4 = 180V
This value is set to the next highest DIP switch setting available based on
the result of the following calculation:

Par 162 [Max Feedback Spd] = 1750 rpm (default)
This value is based on: (180V/50V/2.057) =1.750 (1000)

The reference and feedback resolution = (5250 fpm/25000 counts) = 0.21
fpm/count

Example 4: DC Tachometer with Field Weakening

This example is similar to example 3 except that a field weakening speed of 2500
rpm is configured rather than a base speed of 1750 rpm.

Par 175 [Rated Motor Volt] = 500V (default)

Set Par 45 [Max Ref Speed] = 2500 rpm

Set Par 562 [Anlg Tach Gain] = 1.44

Set Par 585 [Overspeed Val] = 2750 rpm

Set DIP switch S4 = 180V
This value is set to the next highest DIP switch setting available based on
the result of the following calculation:

Set Par 162 [Max Feedback Spd] = 2500 rpm
This value is based on: (180V/50V/1.44) = 2.5 (1000)

The reference and feedback resolution = (7500 fpm/25000 counts) = 0.3
fpm/count

Tachometer

x

Max Motor Speed

x

Overspeed Percentage

=

Scaled Tach Input Volts

(50V/1000 rpm)

(1750 rpm)

(1.1)

96.25V

Tachometer

x

Max Motor Speed

x

Overspeed Percentage

=

Scaled Tach Input Volts

(50V/1000 rpm)

(2500 rpm)

(1.1)

137.5V