Rockwell Automation Publication 20P-UM001K-EN-P - July 2014

Chapter 2

Drive Start Up

28.

Access the “Digital Inputs” group.

29.

Configure the following parameters:

❏ Par 1391 [ContactorControl] - Select the type of contactor(s) used

with the drive: 1 “Contactor” (default, AC input or DC output
contactor), 2 “Contactor+DB” (AC input or DC output contactor
and dynamic brake contactor), or 0 “None”.

Note

: If you select 0 “None” for Par 1391 [ContactorControl], a

“CntactrCflct” alarm will display. The alarm will be resolved and
automatically clear when you complete the Digital Output
configuration below.

Note

: If Par 1391 [ContactorControl] is set to 1 or 2, an Auxiliary

Status contactor must be wired to a digital input (default for digital
input 8).

❏ Par 140 [Digital In8 Sel] - If a contactor is NOT used, set to other

than 31 “Contactor” (for example, 0 “Not Used”).

❏ If an auxiliary status contactor is wired to a digital input, set the

appropriate [Digital Inx Sel] parameter to 31 “Contactor”.

30.

Access the “Digital Outputs” group.

31.

Configure the following parameters:

❏ If a contactor and a dynamic brake resistor are used:

• Par 629 [Relay Out 2 Sel] = 24 “ContactorDB”.

❏ If a neither a contactor nor a dynamic brake resistor are used:

• Par 629 [Relay Out 2 Sel] = Set to other than 24 “ContactorDB”

or 25 “Contactor” (for example, 0 “Not Used”).

• Par 1392 [Relay Out 1 Sel] = Set to other than 24

“ContactorDB” or 25 “Contactor” (for example, 0 “Not Used”).