Installation and Wiring

Chapter 1

Figure 12 - High-impedance Ground

Grounding the Wye secondary neutral through a resistor is an acceptable method
of grounding. In this case, in a short-circuited secondary condition, none of the
output phases to ground will exceed the normal line to line voltage. The resistor
is often used to detect ground current by monitoring the associated voltage drop.

Table 8 - Drive Modifications to Support Ungrounded Wye Neutral or Impedance Grounded
Connections

Figure 13 - Frame A Pulse Transformer Circuit Board S9 Jumper Location

Frame

Circuit Board

Jumper/Connection

Figure to see for Details

A

Pulse transformer (FIR1-xx-xx)

Remove jumper S9

Figure 13

on page

35

B

Pulse transformer (FIR2-xx-xx)

Remove jumper S9

Figure 14

on page

36

C

Pulse transformer (FIR3-xx-xx)

Remove jumper S9

Figure 15

on page

36

Transient noise filter (FIL-31),
200V…500V AC drives

Disconnect the filter board yellow/
green (ground) wire from the PE
connection on the drive chassis

Figure 16

on page

37

Transient noise filter (FIL-57,
FIL-69), 575V…690V AC drives

Remove jumper S1

Figure 17

on page

37

D

Pulse transformer (FIR-D-xx-xx)

Remove capacitors C121 and C122

Figure 18

on page

38

Overvoltage clipping (CFSF-xxx)

Remove jumper S1

Figure 19

on page

38

S9

T01

T04

T02

T05

T03

T06

T1

T4

T2

T5

T3

T6

78 79 35 36 75 76 U2 V2

S4

S3

XY

XR

TR2

TR1

XP

XSW

XSW1

X3

X4

S9

Note: Remove the front covers from the
drive to access the pulse transformer circuit
board. See page

27

for instructions.