Figure 12 - High-impedance Ground
Grounding the Wye secondary neutral through a resistor is an acceptable method
of grounding. In this case, in a short-circuited secondary condition, none of the
output phases to ground will exceed the normal line to line voltage. The resistor
is often used to detect ground current by monitoring the associated voltage drop.
Table 8 - Drive Modifications to Support Ungrounded Wye Neutral or Impedance Grounded
Connections
Figure 13 - Frame A Pulse Transformer Circuit Board S9 Jumper Location
Frame
Circuit Board
Jumper/Connection
Figure to see for Details
A
Pulse transformer (FIR1-xx-xx)
Remove jumper S9
on page
B
Pulse transformer (FIR2-xx-xx)
Remove jumper S9
on page
C
Pulse transformer (FIR3-xx-xx)
Remove jumper S9
on page
Transient noise filter (FIL-31),
200V…500V AC drives
Disconnect the filter board yellow/
green (ground) wire from the PE
connection on the drive chassis
on page
Transient noise filter (FIL-57,
FIL-69), 575V…690V AC drives
Remove jumper S1
on page
D
Pulse transformer (FIR-D-xx-xx)
Remove capacitors C121 and C122
on page
Overvoltage clipping (CFSF-xxx)
Remove jumper S1
on page
S9
T01
T04
T02
T05
T03
T06
T1
T4
T2
T5
T3
T6
78 79 35 36 75 76 U2 V2
S4
S3
XY
XR
TR2
TR1
XP
XSW
XSW1
X3
X4
S9
Note: Remove the front covers from the
drive to access the pulse transformer circuit
board. See page
for instructions.