beautypg.com

Rockwell Automation 23P PowerFlex Digital DC Drive User Manual

Page 295

background image

Rockwell Automation Publication 20P-UM001K-EN-P - July 2014

295

Application Notes

Appendix C

9.

Set the brake slip definition.

Sets the number of encoder or resolver revolutions to define a brake
slippage condition.

10.

Set the brake float tolerance.

Sets the level at which the float timer will start counting.

11.

Set the brake float time.

Sets the time to maintain zero speed with brake open when the run
command has been released.

The drive is now setup and Torque Prove for the mechanical brake control is
activated. The load can now be applied.

Optimize the Speed Loop Tuning

You can now use DriveObserver to optimize the speed loop tuning. Use a 30
second time scaling on the X-axis. Using DriveObserver, setup the following
traces.

Run the crane up and down under full load. Adjust acceleration and deceleration
rates if required.

Parameter

Setting

1110 [Brk Slip Count]

0.25 (Default)

Parameter

Setting

1111 [Float Tolerance]

52.50 RPM

Parameter

Setting

1113 [ZeroSpdFloatTime]

5.000 Secs (Default)

Parameter

Setting

1008 [Spd Reg Fdbk]

Scaled to minimum and maximum speed limits

113 [Ramp Out]

Scaled to minimum and maximum speed limits

200 [Arm Current]

Scaled to current limit value

41 [Current Reg In]

Default scaling

This manual is related to the following products: