background image

MODEL6300

6. 18

MODEL6300

Section 6 Instantaneous value measurement

Section

6

Ɣ Active power P/ Reactive power Q/ Apparent power S

: P1/P2/P3, Q1/Q2/Q3, S1/S2/S3 , max 4 digits
: P, Q, S (total), max 5 digits

Power (*) x VT ratio x CT ratio x 120%

Digit & Decimal point position

900 ~ 999.9

W/Var/VA

999.9

W/Var/VA

1k ~ 9.999k W/Var/VA

9.999 k

W/Var/VA

10k ~ 99.99k W/Var/VA

99.99 k

W/Var/VA

100k ~ 999.9k W/Var/VA

999.9 k

W/Var/VA

1M ~ 9.999M W/Var/VA

9.999 M W/Var/VA

10M ~ 99.99M W/Var/VA

99.99 M W/Var/VA

100M ~ 999.9M W/Var/VA

999.9 M W/Var/VA

1G ~ 9.999G W/Var/VA

9.999 G W/Var/VA

10G ~ 99.99G W/Var/VA

99.99 G W/Var/VA

100G ~ 999.9G W/Var/VA

999.9 G W/Var/VA

1000G ~ 9999 G W/Var/VA

9999 G W/Var/VA

* The table shows values of power corresponding to each voltage and current
range.

Current range

Voltage

range

5.000A

10.00A

20.00A

50.00A

100.0A

200.0A

500.0A

1000A

150.0V

750.0

1.500k

3.000k

7.500k

15.00k

30.00k

75.00k 150.0k

300.0V

1.500k

3.000k

6.000k

15.00k

30.00k

60.00k

150.0k 300.0k

600.0V

3.000k

6.000k

12.00k

30.00k

60.00k

120.0k

300.0k 600.0k

The above listed power values apply to single-phase 2-wire(1ch).The power
for a single-phase 2-wire(2ch)/single-phase 3-wire/ three-phase 3-wire system
will be twice that of the above values. Total power of the individual phases of a
single-phase 2-wire(3ch)/ three-phase 4-wire system will be three times that of
the above values.

Ɣ Power factor PF: PF (whole system), PF1/PF2/PF3 (each phase), 4 digits

Display range

-1.000 ~ 1.000 PF

Ɣ Frequency f: 3 digits

Display range

40.0 ~ 70.0 Hz

Ɣ Neutral current In (A) (only for three-phase 4-wire system): max 5 digits
Decimal point and the unit are same as for Current.