KYORITSU 6300 Instruction Manual User Manual
Page 78
MODEL6300
6. 18
MODEL6300
Section 6 Instantaneous value measurement
Section
6
Ɣ Active power P/ Reactive power Q/ Apparent power S
: P1/P2/P3, Q1/Q2/Q3, S1/S2/S3 , max 4 digits
: P, Q, S (total), max 5 digits
Power (*) x VT ratio x CT ratio x 120%
Digit & Decimal point position
900 ~ 999.9
W/Var/VA
999.9
W/Var/VA
1k ~ 9.999k W/Var/VA
9.999 k
W/Var/VA
10k ~ 99.99k W/Var/VA
99.99 k
W/Var/VA
100k ~ 999.9k W/Var/VA
999.9 k
W/Var/VA
1M ~ 9.999M W/Var/VA
9.999 M W/Var/VA
10M ~ 99.99M W/Var/VA
99.99 M W/Var/VA
100M ~ 999.9M W/Var/VA
999.9 M W/Var/VA
1G ~ 9.999G W/Var/VA
9.999 G W/Var/VA
10G ~ 99.99G W/Var/VA
99.99 G W/Var/VA
100G ~ 999.9G W/Var/VA
999.9 G W/Var/VA
1000G ~ 9999 G W/Var/VA
9999 G W/Var/VA
* The table shows values of power corresponding to each voltage and current
range.
Current range
Voltage
range
5.000A
10.00A
20.00A
50.00A
100.0A
200.0A
500.0A
1000A
150.0V
750.0
1.500k
3.000k
7.500k
15.00k
30.00k
75.00k 150.0k
300.0V
1.500k
3.000k
6.000k
15.00k
30.00k
60.00k
150.0k 300.0k
600.0V
3.000k
6.000k
12.00k
30.00k
60.00k
120.0k
300.0k 600.0k
The above listed power values apply to single-phase 2-wire(1ch).The power
for a single-phase 2-wire(2ch)/single-phase 3-wire/ three-phase 3-wire system
will be twice that of the above values. Total power of the individual phases of a
single-phase 2-wire(3ch)/ three-phase 4-wire system will be three times that of
the above values.
Ɣ Power factor PF: PF (whole system), PF1/PF2/PF3 (each phase), 4 digits
Display range
-1.000 ~ 1.000 PF
Ɣ Frequency f: 3 digits
Display range
40.0 ~ 70.0 Hz
Ɣ Neutral current In (A) (only for three-phase 4-wire system): max 5 digits
Decimal point and the unit are same as for Current.