INSTRUCTION MANUAL

DIGITAL CLAMP METER

KEW SNAP

SERIES

KEW2040  600A AC Only Type
KEW2055 1000A AC/DC Type

1.Features

Designed to meet international safety standards.

IEC61010-1.IEC61010-031:2002 & IEC61010-2-032

Measurement Category (CAT.) IV 600V

Pollution Degree 2

Double molded main body provides comfortable

single handed grip

Data Hold Function

LCD Backlight function to facilitate working at

dimly lit situations. (KEW2055 only)

REL function to indicate measurement variation.

(Current, voltage, Resistance measurement)

MIN/MAX function enables easy reading of min &

max value during measurement.

With Continuity & Diode Check Function

NCV

Non Contact Voltage

Function for wiring

check.

600V input protection.

Sleep function to extend battery life.

With Bar Graph, 6039 counts

2. Safety Warnings

This instrument has been designed, manufactured and

tested according to IEC 61010: Safety requirements for

Electronic Measuring apparatus, and delivered in

the best condition after passed the inspection. This

instruction manual contains warnings and safety

rules which must be observed by the user to ensure

safe operation of the instrument and retain it in safe

condition.

Therefore, read through these operating instructions

before using the instrument.

WARNING

Read through and understand the instructions

contained in this manual before using the

instrument.

Keep the manual at hand to enable quick

reference whenever necessary.

The instrument is to be used only in its intended

applications.

U n d e r s t a n d a n d f o l l o w a l l t h e s a f e t y

instructions contained in the manual.

It is essential that the above instructions are

adhered to.

Failure to follow the above instructions may

cause injury, instrument damage and/or damage

to equipment under test.

The symbol indicated on the instrument means that

the user must refer to the related parts in the manual

for safe operation of the instrument. It is essential to

read the instructions wherever the symbol appears

in the manual.

DANGER is reserved for conditions and actions
that are likely to cause serious or fatal injury.

WARNING is reserved for conditions and actions
that can cause serious or fatal injury.

CAUTION is reserved for conditions and actions
that can cause injury or instrument damage.

Marks listed in the table below are used on this

instrument.

User must refer to the manual.
Instrument with double or reinforced insulation
Indicates that this instrument can clamp on

bare conductors when measuring a voltage

corresponding to the applicable measurement

category, which is marked next to this symbol.
AC

DC
AC & DC

DANGER

Never make measurement on a circuit in which

voltage over AC600V exists.

Do not attempt to make measurement in the

presence of flammable gasses. Otherwise, the

use of the instrument may cause sparking,

which can lead to an explosion.

Transformer jaw tips are designed not to short

the circuit under test. If equipment under test

has exposed conductive parts, however, extra

precaution should be taken to minimize the

possibility of shorting.

Never attempt to use the instrument if its

surface or your hand is wet.

Do not exceed the maximum allowable input of

any measuring range.

Never open the Battery cover during a

measurement.

The instrument is to be used only in its intended

applications or conditions. Otherwise, safety

functions equipped with the instrument doesn

t

work, and instrument damage or serious personal

injury may be caused.

WARNING

Never attempt to make measurement if any

abnormal conditions, such as broken case

and exposed metal parts are found on the

instrument.

Do not rotate the Function Switch while the

test leads are being connected.

Do not install substitute parts or make any

modification to the instrument. For repair or

re-calibration, return the instrument to your

local distributor from where it was purchased.

Do not try to replace the batteries if the

surface of the instrument is wet.

Disconnect all the cords and cables from the

object under test and power off the instrument

before opening the Battery Cover for Battery

replacement.

Verify proper operation on a known source

before use or taking action as a result of the

indication of the instrument.

Use appropriate personal protective equipment

such as insulating gloves, Insulating boots, and

safety glasses.

CAUTION

Set the Function Switch to an appropriate

position before starting measurement.

Firmly insert the test leads.

Disconnect the test leads from the instrument

for current measurement.

Do not expose the instrument to the direct sun,

high temperature and humidity or dewfall.

Altitude 2000m or less. Appropriate operating

temperature is within 0

and 40

.

This instrument isn

t dust & water proofed. Keep

away from dust and water.

Be sure to power off the instrument after use.

When the instrument will not be in use for a

long period, place it in storage after removing

the batteries.

Use a cloth dipped in water or neutral

detergent for cleaning the instrument. Do not

use abrasives or solvents.

Measurement categories

(Over-voltage categories)

To ensure safe operation of measuring instruments,
IEC61010 establishes safety standards for various
electrical environments, categorized as CAT.I to
CAT.IV, and called measurement categories. Higher-
numbered categories correspond to electrical
environments with greater momentary energy,
so a measuring instrument designed for CAT.III
environments can endure greater momentary energy
than one designed for CAT.II.

CAT.Ⅰ

: Secondary electrical circuits connected to an

AC electrical outlet through a transformer or
similar device.

CAT.Ⅱ

: Primary electrical circuits of equipment

connected to an AC electrical outlet by a
power cord.

CAT.Ⅲ

: Primary electrical circuits of the equipment

connected directly to the distribution panel,
and feeders from the distribution panel to
outlets.

CAT.Ⅳ

: The circuit from the service drop to the

service entrance, and to the power meter
and primary over current protection device
(distribution panel).

3. Specification
3-1. Measuring range & accuracy

(accuracy guaranteed at 23

℃±

5

.humidity 45

85%)

AC Current 600A, 1000A Function

Function

Measuring

Range

Accuracy

KEW2040

KEW2055

600A

0-600.0A

±

1.5%rdg

±

5dgt

(50/60Hz)

±

3.5%rdg

±

8dgt

(40-400Hz)

±

1.5%rdg

±

5dgt

(50/60Hz)

±

3.5%rdg

±

8dgt

(40-400Hz)

1000A

0-1000A

N/A

DC Current 600A, 1000A Function

Function

Measuring

Range

Accuracy

KEW2040

KEW2055

600A

0-600.0A

N/A

±

1.5%rdg

±

5dgt

1000A

0-1000A

N/A

AC Voltage Function

Auto-ranging, Input impedance: approx. 10M

Ω)

Range

Measuring

Range

Accuracy

KEW2040

KEW2055

6/60/600V 1-600.0V

±

1.3%rdg

±

4dgt (50/60Hz)

±

3.0%rdg

±

5dgt (40

400Hz)

DC Voltage Function

Auto-ranging, Input impedance: approx. 10M

Ω)

Range

Measuring

Range

Accuracy

KEW2040

KEW2055

600mV/6/

60/600V

0-600.0V

±

1.0%rdg

±

3dgt

Resistance

Continuity/Diode Check

Function

Range

Measuring

Range

Accuracy

KEW2040

KEW2055

600

Ω

/6k/

60k/600k

Ω

6M

Ω

0-600.0k

Ω

±

1.0%rdg

±

5dgt

60M

Ω

6.00M-

60.00M

Ω

±

5%rdg

±

8dgt

Cont Buzzer 0-600.0

Ω

Buzzer sounds at 100

Ω

or less

Diode

Test voltage: 0-2V

Frequency/ DUTY Function

Auto-ranging for

Frequency

Range

Measuring

Range

Accuracy

KEW2040

KEW2055

ACA

40Hz

400Hz

±

0.5%rdg

±

5dgt

ACV

1Hz

10kHz

0.1-99.9%

(Pulse width/Pulse period)

±

2.5%rdg

±

5dgt

Note: Measurable inputs are: 40Vrms@ACV or
50Arms@AC600A, 350A@AC1000A Range

3-2. General Specification

Mode of operation

:

Δ

∑ mode

Display

: max. 6039 counts

     

(Frequency: 9999) & Bar graph

Over-range indication : "OL" displayed when exceeding
the measuring range. (except for AC/DCV and 1000A
Function)

Range switching :

Auto-ranging / Voltage, Resistance Range

Single range / Continuity, Diode check and DUTY

Sample rate

  

: three times per second

Functional construction :

OFF/ACA/ACV/DCV/

Ω

KEW2040

OFF/ACA/DCA/ACV/DCV/

Ω

KEW2055

Keys

:

SELECT(AC/DC switching & /

Ω

/ /

), REL

Δ

,

Hz/DUTY, MIN/MAX, HOLD/ Back Light (KEW2055)

Power source

: DC3V/ R03(UM-4) x 2pcs

Low battery warning : "

" mark is displayed at

   

2.4V

±

0.15V or less.

Temperature & humidity : 23

℃±

5

, relative humidity

accuracy guaranteed 85% or less (no condensation)

Operating temperature :0

40

, relative humidity

& humidity range 85% or less (no condensation)

Storage temperature : -20

60

, relative humidity

& humidity range 85% or less (no condensation)

Current consumption : approx. 12 mA

Sleep Function : Automatically powered off in about

15 min after the last Function switch operation.

Press any key or rotate the Function Switch from
OFF to any position to exit from the Sleep state.

Applicable Standards

IEC 61010-1:2001

Measurement CAT. IV 600V Pollution degree 2

IEC 61010-031:2002, IEC 61010-2-032

EMC

EN 61326

 ・

EN 55022

 ・

EN 61000-4-2 (performance criterion B)

 ・

EN 61000-4-3 (performance criterion B)

Overload Protection

Current Range

: 720A AC/ 10 sec @KEW2040

1200A AC/DC/ 10 sec @KEW2055

Voltage Range

: 720V AC/DC/ 10sec

Resistance Range : 600V AC/DC/ 10sec

Withstand Voltage

6880V AC

TRMS 50/60Hz

/ 5 sec

(between Jaws and electrical circuit/ between internal

circuit and enclosure)

Insulation Resistance : 10M

Ω

or more/ 1000V

 (

between electrical circuit and enclosure

Conductor size

KEW2040: approx. 33mm

KEW2055: approx. 40mm

Dimension

approx. 254(L)

×

82(W)

×

36(D)mm / KEW2055

approx. 243(L)

×

77(W)

×

36(D)mm / KEW2040

Weight : approx.: 300g @ KEW2040

: 310g @ KEW2055

Accessories

Test Leads

Model 7066 / 1 set

Battery R03

UM-4

/ 2pcs

Instruction manual English, Japanese / 1pce

Carriyng Case Model 9094/ 1pcs

3-3. Function Keys

The "

" mark shows available function at each Range.

DC Current Measurement (KEW2055 only)

HOLD SELECT ZERO

Hz/

DUTY

MAX/

MIN

ACA

ACV

-

DCA

-

DCV

-

-

Ω

-

-

-

-

-

-

-

-

-

4. Preparation for measurement
4-1. Checking Battery Voltage

Set the Function Switch to any position other than

"

OFF

" . When the display is clear without "

BATT

" mark,

showing, battery voltage is enough. When the display

is blank or

"

BATT

" mark is indicated, replace the

batteries according to Section 7, Battery Replacement.

CAUTION

The Sleep feature automatically powers the

instrument off in about 15 min after the last

switch or key operation. Therefore, the display

may be blank even with the Function Switch set

to a position other than "

OFF

" . To operate the

instrument in this case, turn the switch back to

the "

OFF

" position, then to any other position,

or press any key. Replace the batteries if nothing

was displayed after above operations.

4-2. Checking Switch Setting & Operation

Confirm the Function Switch is set to the correct

position, the instrument is set to the correct

measurement mode,

and the Data hold function is disabled. Otherwise,

desired measurement cannot be made.

5. Measurement
5-1. AC Current Measurement

DANGER

Never make measurement on a circuit in which

voltage over AC600V exists to avoid getting

electrical shock.

Transformer jaw tips are designed not to short

the circuit under test. If equipment under test

has exposed conductive parts, however, extra

precaution should be taken to minimize the

possibility of shorting.

Do not make measurement with the Battery

Cover removed.

Disconnect the test leads from the instrument for

current measurement.

(1) Set the Function Switch to "

600A

" or "

1000A

"

position. (on KEW2040, only "600A" is available)

AC has been selected by default; press the SELECT

key, when DC has been selected, to change it to

AC. AC mark is displayed at the upper left on the

display. (KEW2055 only)

(2) Press the trigger to open the transformer jaws

and clamp them onto the one conductor under test,

then take the reading on the display. Pressing the

"

Hz/DUTY

" Key switches the indication in following

sequence.

AC Current

Hz

DUTY

Hz/DUTY

Function requires 50A or more at AC600A

Range and 350A or more at AC1000A range.

CAUTION

Max conductor size for KEW2040 is approx dia.

33mm and for KEW2055 is approx dia. 40mm.

During current measurement, keep the trans

former jaws fully closed. Other wise, accurate

measurements cannot be taken.

5-2. DC Current Measurement (KEW2055 only)

DANGER

Never make measurement on a circuit in which

voltage over DC600V exists to avoid getting

electrical shock.

Do not make measurement with the Battery

Cover removed.

(1) Set the Function Switch to "

600A

" or "

1000A

"

position. AC has been selected by default; press

the SELECT key, when AC has been selected, to

change it to DC.

DC mark is displayed at the upper left on the