08/2013 - MA SUMMIT 8800 Vol2 R02 en
SUMMIT 8800
HARDWARE DETAILS
05
5 .1 .6 .2 Alarm output
An alarm output can be set to represent individual alarms or groups of alarms. From the Tree
menu select the required alarm or alarms that the output will represent, the alarm is selected
by enabling the tick box adjacent to each alarm or group of alarms.
Any alarms in the SUMMIT may be combined to one output. E.g. this might be any station or
stream alarm, but it might also one specific alarm, such as a proving alarm.
Figure 35 Configure alarm output
It is possible to reverse the logic (invert high and low) of each output by enabling the Invert tick
box.
5 .1 .6 .3 Status Output
A status output is set to follow a particular variable from the ID data tree.
Figure 36 Configure State output
For valve operation select the Variable to be a manual Valve control value. The Output will then
follow the logic State of the manual Valve Control. Further details on the valve configuration can
be found in paragraph 11.
It is possible to reverse the logic (invert high and low) of each output by enabling the Invert tick
box.
For testing, set the output to OFF. And use the invert tick box to turn the output to ON.