SUMMIT 8800
PROVER
10
Plenum constant R
Defined value for plenum R constant
Plenum constant pressure Defined value for plenum pressure constant
Detector temperature
The use of detector to measure temperature – yes or no
Figure 147 Prover options: general settings, master meter
Proving length section
Proving cycle - start to end based on time or number of pulses
Length of Proving run
Defined limit of pulses or time required for proving length
Meter correction
Correction data for the master meter – MF or K-factor
Meter preset KF
Master meter K-factor value
10 .1 .4 .2 Stability
The prover can be configured to check the stability of volume, pressure and temperature before
the proving sequence is initiated.
Once the proving sequence has been initiated, the prover will wait for the specified minimum
stability duration time (in seconds) before adjusting the prover loop outlet valve, it will then wait
up until a user selectable maximum stability duration time (in seconds) for the flow, pressure
or temperature to stabilise. If the required stabilisation level is not met then the prove will be
aborted.
The parameters for each of the volume, pressure and temperature are: