The PID valve output is configured as an analogue output.

Figure 166 Select the PID valve ID and the Preset keypad setpoint ID

11 .4 Feedback

For most vaves is is important to know if they realy opened or closed after a command has been

given. Limit switches can be mounted or for electrical valves signals are generated in the cirquit

to have two digital status feedback signals: one for open, one for closed.

Feedback valves can be opened and closed by two individual digital status outputs.

The SUMMIT will check if these signals are set within a specified period after a control signal is

given.

Figure 167 Feedback valve

Open and closed duration keypad

The length of time the corresponding command is sent.

Transition duration keypad

Maximum time allowed for the valve to move before a feedback

signal should occur.

Use valve alarms

Select if an alarm must be generated if the transition time is

exceeded.