beautypg.com

6 .8 .1 ratio of specific heats (liquid and gas), 6 .8 .2 viscosity (steam) – KROHNE Summit 8800 Vol 2 User Manual

Page 104

background image

104

www.krohne.com

08/2013 - MA SUMMIT 8800 Vol2 R02 en

SUMMIT 8800

STREAM CONFIGURATION

06

Figure 97 Stream Liquid, gas and steam line density selection

Keypad

The default value as used in the selection. This value may be changed by an operator.

The keypad value is for line density, for liquids also for the temperature and density.

Limits

The alarm limits (max and min) and warning limits (hi and lo) for the line density.

6 .8 .1 Ratio of specific heats (liquid and gas)

Figure 98 Stream ratio of specific heats

Optionally, the ratio of specific heat can be given as a keypad value or calculated using Method 1.

In the following parameters must be specified:

Yv

Ratio of specific heat reference value

K18, K19, K20

Ratio of specific heat constants

Under the viscosity tab the source of viscosity is entered as either keypad or IAPWS IF97 togeth-

er with the actual keypad value if required.

6 .8 .2 Viscosity (steam):

Three options are available for viscosity:

Keypad

The user defined value for this range will be choosen as given.

IAPWS IF97

The viscosity will be calculated to IAPWS IF97

Estimation

Estimation based on temperature and constants to be entered
Viscosity= Visc1+ Visc2*t + Visc3* t2