SUMMIT 8800

STREAM CONFIGURATION

06

Figure 109 Base density selection

The 4 choices provided for the relative density selection are:

None

No relative density calculated

Keypad

A user can enter a fixed value for base density

AGA8

The value will be calculated via AGA8 calculations based on the gas data

Rho air x rd

The value will be calculated by multiplying relative density with base density of air.(see

next page).

Also the keypad value can be entered together with the min, max alarm limits and high, low

warning limits for base density.

Furthermore the compressibility setting can be given:

Figure 110 Compressibility options

The following choices for compressibility can be selected:

Keypad

A fixed user defined value to be entered

AGA8

Using the AGA8 calculation based on the gas data available

SGERG

Using the SGERG calculation based on relative density and combinations of gas data:

rd-Hs-CO2 / rd-Hs-N2 / rd-Hs-CO2-H2 / rd-Hs-N2-H2 / rs-N2-CO2

Also the combustion temperature must be given.

NX19

Using the NX19 calculation based on the gas data available. 3 Versions are available:

Standard / Gost / G9

ISO 6976

Using the ISO 6976 calculation based on the gas data available.

GPA 2172

Using the GPA 2172 calculation based on the gas data available.