5 .1 .6 .1 pulse output – KROHNE Summit 8800 Vol 2 User Manual

Page 57

background image

57

www.krohne.com

08/2013 - MA SUMMIT 8800 Vol2 R02 en

SUMMIT 8800

HARDWARE DETAILS

05

Figure 33 Configure digital output

Select the desired output
Define the output type as follows
Off

Not used

Pulse

Set to generate pulses to the output for e.g. telemetry

Alarm

Alarm indication to e.g. a alarm horn or a scada system

State

Output set to on or off state, e.g. valve operation

Corrected pulse

Used for proving, see paragraph 10. Only available on output 1.

5 .1 .6 .1 Pulse output

Figure 34 Configure pulse outputs

• Select the variable from the pull down ID data tree. This would normally be a counter incre-

ment value.

• The divisor is used to divide the counter increment. So use 10 to have an output of 50Hz for

500 increments per second.

• Select the maximum frequency of the output, from 50 to 2 Hz.

• Select the duty cycle from 25%, 50% or 75%. This means that e.g. 25% of the time the signal

will be raised, the other 75% it will be low. Typically 50% will be chosen.

• It is possible to reverse the logic (invert high and low) of each output by enabling the Invert

tick box.