STREAM CONFIGURATION

06

None

No functionality or transmitter selected, the option will be skipped.

Keypad

The user defined value for this range will be chosen.

Sensor 1-3

The transmitter value, as configure in hardware, will be used.

Average

Average value of all transmitters (selected in DP sensor) will be used.

Serial

Value as sent by Modbus e.g. from a PLC, or smart transmitter will be used.

Last good value

The last good value known before loss of signal will be used.

Station

A temperature as defined under the station/temperature tab

A selection could look like:

Figure 94 Stream temperature selection

Sensors

The number of sensors connected to the SUMMIT

Keypad

The default value which can be used in the selected

Max, Min

The alarm limits for the temperature. If only one of the two must be used, see

advanced.

Hi, Lo

The warning limits for the temperature. If only one of the two must be used, see

advanced.

Select

The 6 choices for selection of the temperature source

6 .7 .1 Sensor calibration constants

The calibration range and offset are the scaling factors for the transmitter, determined during

the calibration of the transmitter. As this is a multiplier to the normal transmitter range and

offset, this is not a mandatory setting, but a software calibration. This is used to correct the

transmitter value without actually calibrating the transmitter itself. The advantage is that the

changes will appear in the audit log.

This setting is also ideal for simulation purposes. With it, the transmitter can be set to any value

without an actual transmitter connected.

Figure 95 Stream temperature calibration constants

Range

Default value is 1. This is a multiplier to the actual transmitter range.

Offset

Default value is 0. This is an offset to the actual transmitter range.