SUMMIT 8800

CONFIGURATOR

04

Figure 20 Configuration version

NOTE:

The version must match the firmware loaded in the SUMMIT 8800. See Appendix 1: software

versions.

In the SUMMIT 8800 it is possible to define one to five different streams (or runs) plus a prover.

Each of these streams is independent from the other. Each can be any metering medium (gas,

liquid or steam) and any meter type: turbine, ultrasonic, Coriolis, orifice etc. (see next para-

graphs for details). Also each stream can have a different engineering unit: Metric or USC (US

Customary) or a mix of them.

The prover can be a master meter, but for liquid it can also be a small volume (or compact)

prover and a uni- or bidirectional prover.

For a new application select the flow computer type (machine type). This will normally be

“Standard”, but if proving is required select gas prover or liquid prover. Then select per stream,

the type of metering; in this case a gas turbine and a liquid Coriolis.

Figure 21 Configuration machine type