beautypg.com

11 .1 analog – KROHNE Summit 8800 Vol 2 User Manual

Page 151

background image

151

www.krohne.com

08/2013 - MA SUMMIT 8800 Vol2 R02 en

SUMMIT 8800

VALVES

11

11 .1 Analog

A 4-20mA output will be used to control the valve. This value can be set either viamodbus or via

the front panel of the flow computer.

Figure 159 Analog valve

Keypad value

Value used if no set point is set.

Maximum output

The maximum valve opening percentage for 20 mA. Normally 100%: open.

Minimum output

The minimum valve opening percentage for 0 mA. Normally 0%: closed.

NOTE: Maximum and minimum values can be configured to prevent the output either fully open-

ing or fully closing by setting the limits within the band set when configuring the output.

Please note that the actual hardware connection must be defined as an analog output in the

hardware section (see volume 1).

The actual control of the valve must also be defined (see also volume 3):

• As a fixed keypad value, entered above

• In the modbus list to remotely control the value

• On display to locally control the valve

Select the control ID as follows:

Figure 160 Analog valve setpoint

The valve output is configured as an analogue output.