10 .1 .3 alarm settings – KROHNE Summit 8800 Vol 2 User Manual
Page 137
137
www.krohne.com
08/2013 - MA SUMMIT 8800 Vol2 R02 en
SUMMIT 8800
PROVER
10
Figure 140 Prover temperature
Inlet unit
Temperature inlet units
Outlet unit
Temperature outlet units
Prover temperature selection
Prover temperature taken from input, output, average (I/O), or line
Inlet and outlet deviation
Temperature inlet and outlet deviation limit
Inlet and outlet deviation time
Inlet and outlet deviation timeout
Prover line deviation
Line temperature deviation limit
Temperature line deviation time Line temperature deviation timeout
10 .1 .2 .2 Inlet and outlet temperature
For details, see stream temperature.
10 .1 .3 Alarm settings
Liquid
Gas
Steam
The re-prove cycle and the start of prove cycle work on the same principles. After the previous
cycle and before a (re-)prove cycle is carried out, the flow computer checks the stability of the
parameters to ensure that they are still within the define limits. Should any one of these limits
be exceeded, the (re-)prove function will stop, and a report generated. A (re-)prove is also initi-
ated should the parameters deviate during a prove cycle already in progress.
Here the absolute limits are configured: