SUMMIT 8800

PROVER

10

Figure 140 Prover temperature

Inlet unit

Temperature inlet units

Outlet unit

Temperature outlet units

Prover temperature selection

Prover temperature taken from input, output, average (I/O), or line

Inlet and outlet deviation

Temperature inlet and outlet deviation limit

Inlet and outlet deviation time

Inlet and outlet deviation timeout

Prover line deviation

Line temperature deviation limit

Temperature line deviation time Line temperature deviation timeout

10 .1 .2 .2 Inlet and outlet temperature

For details, see stream temperature.

10 .1 .3 Alarm settings

Liquid

Gas

Steam

The re-prove cycle and the start of prove cycle work on the same principles. After the previous

cycle and before a (re-)prove cycle is carried out, the flow computer checks the stability of the

parameters to ensure that they are still within the define limits. Should any one of these limits

be exceeded, the (re-)prove function will stop, and a report generated. A (re-)prove is also initi-

ated should the parameters deviate during a prove cycle already in progress.

Here the absolute limits are configured: