beautypg.com

6 .8 .8 .1 z-table – KROHNE Summit 8800 Vol 2 User Manual

Page 108

background image

108

www.krohne.com

08/2013 - MA SUMMIT 8800 Vol2 R02 en

SUMMIT 8800

STREAM CONFIGURATION

06

Figure 105 Gas Line density Z-equation method

The following formula’s for compressibility can be selected:

Keypad

A fixed user defined value to be entered

AGA8

Using the AGA8 calculation based on the gas data available

SGERG

Using the SGERG calculation based on relative density and combinations of gas data:

rd-Hs-CO2 / rd-Hs-N2 / rd-Hs-CO2-H2 / rd-Hs-N2-H2 / rs-N2-CO2

Also the combustion temperature must be given.

NX19

Using the NX19 calculation based on the gas data available. 3 Versions are available:

Standard / Gost / G9

Z Table

A table will appear to enter the compressibility against pressure and temperature.

6 .8 .8 .1 Z-table

If a Z-table is selected for compressibility (under line density/ Z equation tab), an additional icon

“Z-table” will appear in the left hand list:

Liquid

Gas

Steam

This page is used to define the compressibility as a table of up to 50 pressures and 50 tempera-

tures: