70

If you do not wish to monitor the energy yield of a device and want to avoid receiv-
ing error messages, set the “Energy” tolerance to 0 %.

Example of daily energy yield comparison

This system comprises 4 devices, and the energy tolerance is set to 90 %.

Device Yield Message

Comment

A

2.2 kWh

None

Device operating normally

B

1.7 kWh

Error

Yield below tolerance Warning message

C

0 kWh

Offline

Device not operating Error message

D

2.1 kWh

None

Device operating normally

System

6.0 kWh

Average

2.0 kWh

Average device yield

Tolerance

1.8 kWh

Minimum yield expected of a device to avoid er-
ror message


Average: 2.0

kWh

Tolerance:

90

%

=> Minimum energy yield:

1.8 kWh

Devices that have not yielded any energy by the end of the day are not
taken into account when the average is computed.

The percentage under “Communication” indicates the expected minimum ratio of
data packets that must have been transmitted successfully.

The value under “RIso Failure” indicates the required minimum insulation resis-
tance, short of which an error message is generated.