SMA Sunny Boy Control User Manual
Page 154
Sunny Boy Control
SMA Technologie AG
User Manual
SUNBC
-
14
:
NE0206
150
The combination of the number of measuring channels and measuring intervals results
in the following storage capacities.
Measuring channel storage capacity
Chan-
nels
Cycles Spot
values
2
Measuring interval
1–5 inv. 50 inv. 5 min. 10 min. 15 min. 30 min. 60 min. 120 min
.
Hours
(approx.)
Days
1
19255 27 321 134 267 401 802 1605
3209
2
15906 22 265 110 221 331 663 1326
2651
3
13550
19 226 94 188 282 565
1129
2258
4
11801
16 197 82 165 246 492 983
1967
5
10453
15 174 73 145 218 436 871
1742
10
6652 9 111 46 92 139 277 554
1109
15
4878 7 81 34 68 102
203
406
813
20
3851 5 64 27 53 80 160
321
642
25
3181 4 53 22 44 66 133
265
530
50
1702 2 28 12 24 35 71 142
284
100
882 1,2 15 6 12 18 37 73 147
150
595 0,8 10 4 8 12 25 50 99
200
449
0,6 7 3 6 9 19
37
75
250
360
0,5 6 3 5 8 15
30
60
Table 10.2: Storage depth in hours and days
Changing channels reduces the current storage capacity by approximately 0.5 % per
configuration change.
If a Sunny Boy Control manages 50 devices, the preset settings (3 channels per de-
vice, 15-minute measuring interval) result in a storage depth of about 12 days.
2
Saving time for 1–5 inverters: 5 seconds
Saving time for 50 inverters: 60 seconds