Sunny Boy Control

SMA Technologie AG

User Manual

SUNBC-14:NE0206

114

You’re measuring Iac (the current in ampere) with AIN-1 and Vac (the
voltage in volts) with AIN-2 on the AC side. Using two variables, Pac (the
power output in watts) can be calculated, and using integration, Eac (the
energy in kWh) can be calculated. One kilowatt being 1,000 watts and
one hour being 3,600 seconds, Ws are converted into kWh by division
through 3.6E6 (corresponding to 1000 * 3600).

AIN-1: +Iac, A
AIN-2: +Uac, V

VAR-1: +Pac, W, =[Iac]*[Uac]
VAR-2: +Eac, kWh, =INT([+Pac]/3.6E6)

Hardware-Based Configuration

[ Variable 1 ]

Function…

Function of the variable

…activated

deactivated,

activated

---------------Š

Name…

………+PacMax

Name of the channel

Unit…

…………………kW

Measuring unit

Formula…

…=MAX([Pac])

Formula to be calculated

Fig. 7.20: Configuration of variables