Operating settings for reclosing, Operating settings for reclosing -31, Figure 4-34. reclosing screen -31 – Basler Electric BE1-851 User Manual
Page 87: Table 4-15. bestlogic settings for reclosing -31

used. Then, select the BESTlogic variable, or series of variables to be connected to the input. Select
Save when finished to return to the BESTlogic Function Element screen. For more details on the
BESTlogic Expression Builder, see Section 7, BESTlogic Programmable Logic. Select Done after the
settings have been completely edited.
Table 4-15 summarizes the BESTlogic settings for Reclosing.
Table 4-15. BESTlogic Settings for Reclosing
Function
Range/Purpose
Default
Mode
0 = Reclosing disabled
1 = Standard power-up operation. After power-up, the STATUS logic must
be TRUE for the Reset time delay or the recloser automatically goes
to Lockout. If the STATUS logic stays TRUE for reset time delay, the
recloser goes to Reset.
2 = Power-up to close. If the recloser was in the Reset state when power
was lost and when power is restored the STATUS logic is FALSE
(breaker open) and the RI logic is TRUE, the recloser will initiate the
first reclose operation. If the STATUS logic stays TRUE for the reset
time delay, the recloser goes to Reset.
0
RI
OR logic term to initiate the operation of the reclosing function.
0
STATUS
OR logic term to indicate breaker status.
TRUE/1 = closed, FALSE/0 = open.
0
WAIT
OR logic term to momentarily disable but not reset the recloser.
0
BLK/DTL OR logic term to disable the recloser (drive to lockout).
0
Operating Settings for Reclosing
Operating settings are made using BESTCOMS. Figure 4-34 illustrates the BESTCOMS screen used to
select operational settings for the reclosing element. To open the screen, select Reclosing from the
Screens pull-down menu. Alternately, settings may be made using the S
Settings can also be made from the front panel HMI using Screens 5.x.4.1 through 5.x.4.5 where x equals
1 for Setting Group 0, 2 for Setting Group 1, 3 for Setting Group 2, and 4 for Setting Group 3.
Figure 4-34. Reclosing Screen
9289900990 Rev R
BE1-851 Protection and Control
4-31