APPENDIX B • COMMAND CROSS-REFERENCE
Introduction
This appendix lists all ASCII commands, command syntax, brief command descriptions, and any
corresponding HMI screens. Commands are organized by function in the following groups and tables:
•
Miscellaneous (Table B-1)
•
Metering (Table B-2)
•
Control (Table B-3)
•
Report (Table B-4)
•
Setting (Table B-5)
•
Alarm (Table B-6)
•
General Setting (Table B-7)
•
Breaker Monitor and Setting (Table B-8)
•
Programmable Logic Setting (Table B-9)
•
User Programmable Name Setting (Table B-10)
•
Protection Setting (Table B-11)
•
Global (Table B-12)
An entry of x in the HMI Screen column represents multiple entry possibilities such as 0, 1, 2, or 3 for
setting groups and 43, 143, 243, or 343 for virtual switches.
Table B-1. Miscellaneous Commands
ASCII Command
Function
HMI Screen
ACCESS[={password}]
Read/Set access level in order to change
settings.
N/A
EXIT
Exit programming mode.
N/A
HELP {cmd} or H {cmd}
Obtain help with command operation.
N/A
Table B-2. Metering Commands
ASCII Command
Function
HMI Screen
M
Read all metered values.
N/A
M-I[{phase}]
Read metered current in primary unit.
3.1 - 3.2
Table B-3. Control Commands
ASCII Command
Function
HMI Screen
CO-{control}[={mode}]
Control operation.
N/A
CS-control[={mode}]
Control selection.
N/A
CS/CO-x43
Control virtual switches.
2.1.1 - 2.1.4
CS/CO-101
Control breaker control switch.
2.2.1
CS/CO-GROUP
Control group.
2.3.1
CS/CO-OUTn
Control output n.
2.4.1
Table B-4. Report Commands
ASCII Command
Function
HMI Screen
RA[=0]
Report/Reset alarm information.
1.3
RA-LGC[=0]
Report/Reset logic alarm information.
N/A
RA-MAJ[=0]
Report/Reset major alarm information.
N/A
RA-MIN[=0]
Report/Reset minor alarm information.
N/A
RA-REL[=0]
Report/Reset relay alarm information.
N/A
RB
Read breaker status.
4.3.1 - 4.3.2
RB-DUTY[{phase}[={%duty}]]
Read/Set breaker contact duty log.
4.3.2
9289900990 Rev R
BE1-851 Command Cross-Reference
B-1