Basler Electric BE1-851 User Manual
Page 256

SG-DATADUMP Command
Purpose:
Report/Set fault record DATADUMP to COM1
Syntax:
SG-DATADUMP[={mode}] where mode is 0/1 (disabled/enabled)
Example:
SG-DATADUMP or SG-DATADUMP=1
Reference:
Section 6, Reporting and Alarms, Fault Reporting
SG-DI Command
Purpose:
Read/Set demand current interval
Syntax:
SG-DI[p][={interval}] where p=P/N/Q, interval=0-60 (min)
Example:
SG-DI or SG-DIP=15 or SG-DIN=1
Reference:
Section 6, Reporting and Alarms, Demand Functions
SG-DST Command
Purpose:
Read/Set Daylight Saving Time (DST) type
Syntax:
SG-DST[=1/2] where 1 means floating date, and 2 means fixed date
Example:
SG-DST, SG-DST=1, SG-DST=2
Reference: Section 6, Reporting and Alarms, Clock
SG-DSTSTART Command
Purpose:
Read/Set settings for start of Daylight Saving Time
Syntax:
SG-DSTSTART[={Mo,D,H,M,O}] where Mo=Month, D=Day of week (or month), H=Hour,
M=Min, O=# of occurrence of 'D' in the month]
Example:
SG-DSTSTART, SG-DSTSTART=3,1,2,0,1 (For 2AM Mar 1) or SG-
DSTSTART=4,0,2,15,2 (For 2:15AM on 2nd Sunday in April)
Reference: Section 6, Reporting and Alarms, Clock
SG-DSTSTOP Command
Purpose:
Read/Set settings for end of Daylight Saving Time
Syntax:
SG-DSTSTOP[={Mo,D,H,M,O}] where Mo=Month, D=Day of week (or month), H=Hour,
M=Min, O=# of occurrence of 'D' in the month]
Example:
SG-DSTSTOP, SG-DSTSTOP=11,21,3,15,1 (For 3:15AM Nov. 21) or SG-
DSTSTOP=11,2,23,20,1 (For 11:20AM on 1st Tue in Nov.)
Reference: Section 6, Reporting and Alarms, Clock
SG-FREQ Command
Purpose:
Read/Enter power system Frequency
Syntax:
SG-FREQ[={freq(HZ)}]
Example:
SG-FREQ=60 or SG-FREQ=50
Reference:
Section 3, Input and Output Functions, Current Inputs
SG-HOLD Command
Purpose:
Read/Program Output Hold operation
Syntax:
SG-HOLD[n][={1/0 hold ena}] where 1=TRUE, 0=FALSE
Example:
SG-HOLD or SG-HOLD1=1 or SG-HOLD2=0
Reference:
Section 3, Input and Output Functions, Outputs
SG-ID Command
Purpose:
Read/Set relay ID and station ID used in reports
Syntax:
SG-ID[={relayID(up to 30 char)},{StationID(up to 30 char)}]
Example:
SG-ID=448,SUBSTATION3 or SG-ID=BUS851, POWERPOINT_SUBSTATION
Reference:
Section 6, Reporting and Alarms, Relay Identifier Information
11-14
BE1-851 ASCII Command Interface
9289900990 Rev R