Setting command, Alarm setting commands, Setting command -12 – Basler Electric BE1-851 User Manual
Page 254: Alarm setting commands -12
RS Command
Purpose:
Read/Reset Sequence of Events Record Data
Syntax:
RS[-n/Fn/ALM/IO/LGC/NEW][=0] where n=# of events and Fn=fault record #
Example:
RS (displays a directory of all event records in memory)
RS-23 (view SER report for last 23 events)
RS-F12 (view SER report associated with fault record 12)
RS-ALM (view all SER report ALARM events since RS=0 reset)
RS-IO (view all SER report INPUT OUTPUT events since RS=0 reset)
RS-LGC (view all SER report LOGIC events since RS=0 reset)
RS-NEW (view all SER report events since RS=0 reset)
RS=0 (reset NEW records counter)
Reference:
Section 6, Reporting and Alarms, Sequence of Events Recorder
Setting Command
S Command
Purpose:
Read all relay setting parameters
Syntax:
S
Example:
S
Reference:
Section 11, ASCII Command Interface, Settings (S) Command Descriptions
Alarm Setting Commands
SA Command
Purpose:
Read all alarm settings for Major and Minor alarms
Syntax:
SA
Example:
SA
Reference:
Section 6, Reporting and Alarms, Alarms Function
SA-BKR Command
Purpose:
Read/Set breaker alarm settings
Syntax:
SA-BKR[n][={mode},{alarm limit}] where mode=0-3(disabled/%duty/#op/clr) and alarm
limit=0 means disabled
Example:
SA-BKR or SA-BKR1=1,80 or SA-BKR2=2,250, or SA-BKR3=3,6c
Reference:
Section 6, Reporting and Alarms, Breaker Monitoring
SA-DI Command
Purpose:
Read/Set demand alarm settings
Syntax:
SA-DI[p][={alarm level}] where p=P/N/Q, alarm level=Secondary Amps
Example:
SA-DI or SA-DIP=8.0 or SA-DIN=2.4
Reference:
Section 6, Reporting and Alarms, Demand Functions
SA-LGC Command
Purpose:
Read/Set logic alarm setting mask
Syntax:
SA-LGC[={alarm num 1}[/{alarm num 2}]...[/{alarm num n}]]
Example:
SA-LGC or SA-LGC=2/6/7/10/11
Reference:
Section 6, Reporting and Alarms, Alarms Function
SA-MAJ Command
Purpose:
Read/Set major alarm setting mask
Syntax:
SA-MAJ[={alarm num 1}[/{alarm num 2}]...[/{alarm num n}]]
Example:
SA-MAJ or SA-MAJ=1/3/5/12
Reference:
Section 6, Reporting and Alarms, Alarms Function
11-12
BE1-851 ASCII Command Interface
9289900990 Rev R