Global commands, Global commands -18 – Basler Electric BE1-851 User Manual
Page 260
![background image](https://www.manualsdir.com/files/773789/content/doc260.png)
SP-79ZONE Command
Purpose:
Read/Set 79 Zone Sequence Logic
Syntax:
SP-79ZONE[={zone pickup logic}]
Example:
SP-79ZONE or SP-79ZONE=50TPPU+50TNPU+150TPPU+150TNPU
Reference:
Section 4, Protection and Control, Reclosing
SP-BF Command
Purpose:
Read/Set the Breaker Failure Timer Setting
Syntax:
SP-BF[={time}[m/s/c]] where m=msec,s=sec,c=cycle
Example:
SP-BF or SP-BF=50m or SP-BF=3c
Reference:
Section 4, Protection and Control, Breaker Failure Protection
SP-CURVE Command
Purpose:
Read/Set the user programmable 51 curve parameters
Syntax:
SP-CURVE[={A},{B},{C},{N},{R}]
Example:
SP-CURVE or SP-CURVE=1.0,0,0,2.5,0
Reference:
Section 4, Protection and Control, Overcurrent Protection
SP-GROUP Command
Purpose:
Read/Program auxiliary setting group 1-3 operation
Syntax:
SP-GROUP{g}=[{sw_time},{sw_level},{ret_time},{ret_level},{prot_ele}]
Example:
SP-GROUP, SP-GROUP1=10,75,10,50,51P or SP-GROUP3=0,0,0,0,793
Reference:
Section 4, Protection and Control, Setting Groups
Global Commands
GS-PW Command
Purpose:
Read/Set Password and password access port(s)
Syntax:
GS-PW[{t}[={password},{com ports(0/1/2)}]] where t=G/S/C/R
Example:
GS-PWG=TEST,0 or GS-PWS=XYZ,1/2
Reference:
Section 9, Security
11-18
BE1-851 ASCII Command Interface
9289900990 Rev R