Breaker monitor setting commands, General setting commands, Breaker monitor setting commands -13 – Basler Electric BE1-851 User Manual
Page 255: General setting commands -13

SA-MIN Command
Purpose:
Read/Set minor alarm setting mask
Syntax:
SA-MIN[={alarm num 1}[/{alarm num 2}]...[/{alarm num n}]]
Example:
SA-MIN or SA-MIN=2/6/7/10/11
Reference:
Section 6, Reporting and Alarms, Alarms Function
SA-RESET Command
Purpose:
Read/Set Programmable Alarms Reset logic
Syntax:
SA-RESET[={rst alm logic}]
Example:
SA-RESET or SA-RESET=VO1
Reference:
Section 6, Reporting and Alarms, Alarms Function
Breaker Monitor Setting Commands
SB Command
Purpose:
Read all breaker settings
Syntax:
SB
Example:
SB
Reference:
Section 6, Reporting and Alarms, Breaker Monitoring
SB-DUTY Command
Purpose:
Read/Set Breaker Contact Duty where mode = 0/1/2 (disabled/I/I^2)
Syntax:
SB-DUTY[={mode},{dmax},{BLKBKR logic}]
Example:
SB-DUTY=1,60E3,IN5
Reference:
Section 6, Reporting and Alarms, Breaker Monitoring
SB-LOGIC Command
Purpose:
Read/Set Breaker Contact Logic
Syntax:
SB-LOGIC[={breaker close logic}]
Example:
SB-LOGIC=IN1 (IN1=52a) or SB-LOGIC=/IN2 (IN2=52b)
Reference:
Section 6, Reporting and Alarms, Breaker Monitoring
General Setting Commands
SG Command
Purpose:
Read all general settings
Syntax:
SG
Example:
SG
Reference:
Section 11, ASCII Command Interface, Settings (S) Command Descriptions
SG-CLK Command
Purpose:
Read/Program format of date and time display
Syntax:
SG-CLK[={date format(M/D)},{time format(12/24)},{dst enable(0/1)}]
Example:
SG-CLK=D,12,1 or SG-CLK=M,24,0
Reference:
Section 6, Reporting and Alarms, Clock
SG-COM Command
Purpose:
Read/Set serial communications protocol
Syntax:
SG-COM[#[={baud},A{addr},P{pglen},R{reply ack},X{XON ena}]]
Example:
SG-COM0=9600 or SG-COM1=9600,A0,P24,R1,X1
Reference:
Section 11, ASCII Command Interface, Settings (S) Command Descriptions, Configuring
the Serial Port Communication Protocol
9289900990 Rev R
BE1-851 ASCII Command Interface
11-13