Exit command, Settings (s) command descriptions, Reading all settings – Basler Electric BE1-851 User Manual
Page 246: Exit command -4, Settings (s) command descriptions -4, Reading all settings -4
![background image](https://www.manualsdir.com/files/773789/content/doc246.png)
ACCESS Command Examples:
1. A valid password is entered.
Sent:
ACCESS=OPENUP
Received:
ACCESS GRANTED : GLOBAL
2. An invalid password is entered.
Sent:
ACCESS=POENUP
Received:
ACCESS DENIED
INVALID PASSWORD
3. The current access privilege is read.
Sent:
ACCESS
Received:
ACCESS : GLOBAL
EXIT Command
If changes have been made, the new data will be saved or discarded after using the EXIT command.
Prior to saving or discarding any changes, you must confirm that you wish to exit the programming mode.
There are three exit options: Y (YES), N (NO), or C (CONTINUE).
EXIT Command
Purpose:
Exit the programming mode.
Syntax:
EXIT (Note: Relay will prompt for verification.)
Example:
EXIT
Comments:
It’s important to make all programming changes before executing the EXIT command.
This prevents a partial or incomplete protection scheme from being implemented.
When access privileges are obtained, all programming changes are made to a temporary, scratchpad
copy of relay settings. These changes aren’t saved to nonvolatile memory and initiated until the EXIT
command is invoked and confirmed. After the EXIT command is entered, the relay prompts to confirm that
the new data should be saved. Three options, Y, N, or C are available. Entering Y will save the data. If N
is entered, the relay will clear the changes and resume operating with the old settings. Entering C will
abort the EXIT command and allow programming to continue.
EXIT Command Example:
Release programming privileges and save settings changes.
Sent:
EXIT
Received:
SAVE CHANGES (Y/N/C)?
Prompt to save YES, NO, or CONTINUE
Sent:
Y
Confirmation to SAVE CHANGES
Received:
CHANGES SAVED
Confirmation that CHANGES WERE SAVED
Settings (S) Command Descriptions
Reading All Settings
All user programmable settings can be listed using the S command. This read-only command is useful for
documenting relay status during installation. The settings retrieved by the S command can be saved to a
standard text file and sent to another relay to be configured with the same settings. This type of settings
transfer takes less than one minute.
S Command
Purpose:
Read all relay setting parameters.
Syntax:
S
Example:
S
11-4
BE1-851 ASCII Command Interface