BUS Logic Settings and Equations for Sensing Input Type H Relays
SL-N=BUS
SL-50TP = 1,IN2
SL-50TN = 1,IN2
SL-50TQ = 1,IN2
SL-150TP = 0,0
SL-150TN = 0,0
SL-150TQ = 0,0
SL-51P = 1,0
SL-51N = 1,0
SL-51Q = 1,0
SL-62=1,VO8,0
SL-162=0,0,0
SL-79 = 0,0,0,0,0
SL-BF = 0,0,0
SL-GROUP = 2,IN3,0,0,0,0
SL-43 = 0
SL-143 = 0
SL-243 = 0
SL-343 = 2
SL-101 = 1
SL-VOA = ALMMAJ
SL-VO1 = 101T+VO8*/SG0+62+VO11*VO15
SL-VO2 = 101C
SL-VO3 = 0
SL-VO4 = VO9*SG0*/VO15
SL-VO5 = VO11*SG1*/VO15
SL-VO6 = 0
SL-VO7 = 0
SL-VO8 = 51PT+51NT+51QT
SL-VO9 = 50TPT+50TNT+50TQT
SL-VO10 = 0
SL-VO11 = 50TPT+50TNT+50TQT+51PT+51NT+51QT
SL-VO12 = 50TPPU+50TNPU+50TQPU+51PPU+51NPU+51QPU
SL-VO13 = SG1
SL-VO14 = 0
SL-VO15 = /IN4+343
BUS Logic Settings and Equations for Sensing Input Type H Relays
SL-N=BUS
SL-50TP = 1,IN2
SL-50TN = 1,IN2
SL-150TP = 0,0
SL-150TN = 0,0
SL-250TN = 0,0
SL-350TN = 0,0
SL-51P = 1,0
SL-51N = 1,0
SL-151N = 0,0
SL-62 = 1,VO8,0
SL-162 = 0,0,0
SL-79 = 0,0,0,0,0
SL-BF = 0,0,0
SL-GROUP = 2,IN3,0,0,0,0
SL-43 = 0
8-52
BE1-851 Application