Table 8-25. backup contact sensing input logic -53, Table 8-26. backup function block logic -53 – Basler Electric BE1-851 User Manual
Page 209
![background image](https://www.manualsdir.com/files/773789/content/doc209.png)
SL-143 = 0
SL-243 = 0
SL-343 = 2
SL-101 = 1
SL-VOA = ALMMAJ
SL-VO1 = 101T+VO8*/SG0+62*SG1+VO11*VO15
SL-VO2 = 101C
SL-VO3 = 0
SL-VO4 = VO9*SG0*/VO15
SL-VO5 = VO11*SG1*/VO15
SL-VO6 = 0
SL-VO7 = 0
SL-VO8 = 51PT+51NT
SL-VO9 = 50TPT+50TNT
SL-VO10 = 0
SL-VO11 = 50TPT+50TNT+51PT+51NT
SL-VO12 = 50TPPU+50TNPU+51PPU+51NPU
SL-VO13 = SG1
SL-VO14 = 0
SL-VO15 = /IN4+343
Table 8-25. BACKUP Contact Sensing Input Logic
Input
Purpose
Name Label
State Labels
Energized
De-Energized
IN1
52b Breaker Status.
BREAKER
OPEN
CLOSED
IN2
Put relay in feeder backup mode when
feeder relay out of service is detected
by open contact.
FEEDER_OK
NORMAL
FDR_OOS
IN3
Breaker failure initiate by external
relays.
BFI
INI
NORMAL
IN4
Put the relay in test mode so that
reclosing and breaker failure are
disabled when IN4 is de-energized.
TESTDISABL
NORMAL
TSTMODE
Table 8-26. BACKUP Function Block Logic
Function
Purpose
BESTlogic
Expression
Mode
Setting
50TP
Used for instantaneous phase overcurrent protection.
0
1 (enabled)
50TN
Used for instantaneous neutral overcurrent protection.
0
1 (enabled)
50TQ
Used for instantaneous negative-sequence
overcurrent protection.
0
1 (enabled)
150TP
Used for instantaneous phase overcurrent protection.
0
1 (enabled)
150TN
Used for instantaneous neutral overcurrent protection.
0
1 (enabled)
150TQ
Used for instantaneous negative-sequence
overcurrent protection.
0
1 (enabled)