Basler Electric BE1-851 User Manual
Page 8

Application Firmware
Version and Date
Change
3.43.09, 03/03
•
Added the capability of changing Modbus Password Security with the
ASCII command.
•
Enhanced the 3
rd
parameter {C} for the SP-CURVE command (user
programmable time curve).
•
Insured year change update with IRIG connected, under all conditions.
3.43.07, 03/02
•
Enhanced fault data capture.
•
Improved operation of the front panel Reset key with resettable data.
•
Improved the accuracy of oscillographic waveform amplitude.
•
Enhanced SA-BKR mode; more than one setting can be entered.
•
Improved the display of the reclose cycle.
•
Improved settings change capability.
•
Automatically display the Target screen on the HMI after fault.
•
Added operation of the 43 switches on the HMI scroll list.
3.43.06, 02/02
2.43.06, 02/02
•
Improved accuracy of oscillographic waveform amplitude
measurement.
•
Added functionality of DNP Version 2 with BESTCOMS.
3.43.05, 02/02
2.43.05, 02/02
•
Improved modes of operation for SA-BKR command used to read or set
alarm settings.
•
Changed alarm functionality so that an alarm threshold value of zero
will disable the alarm.
•
Mode settings entered with multiple digits now return an error. Only one
digit may be entered for a mode setting.
•
Improved the BE1-851 to prevent “lockup” from issuing too many
settings changes at one time.
3.43.00, 02/00
•
Updated the GF-VER and RG-VER commands to report Model Number
BE1-851G for style type Gxxxxx and Model Number BE1-851 for style
type Hxxxxx.
•
Updated to support sensing type G (Florida Power Light) which
replaces 51Q with 151N, 50TQ with 250TN, and 150TQ with 350TN.
(This hex file version only works with style type Hxxxxx.)
3.42.01, 11/99
•
Added DNP 3.0, Level 2 compliance. Requires Version 3.xx hardware.
•
Added support for Version 3 hardware with additional memory.
•
Oscillographic recording is as follows:
Feature
Version 3.xx
Number of Oscillographic Records 16
Length of Oscillographic Records
15 cycles each
Sample Resolution
24 samples/cycle
•
Improved target reporting function.
•
The trip LED only latches when there are targets to be displayed on the
HMI. The “pickup” condition, indicated by the Trip LED flashing, is now
a higher priority than latching to indicate that targets are being
displayed on the HMI.
•
Improved HMI Target screen format. Screen now reports targets in a
text format. Additional information such as fault current magnitudes and
time and date of the fault were moved to a lower menu branch so that
the targets are all that is displayed unless the user wants more detail.
•
Added functionality to reset targets using a programmable logic
expression in addition to the HMI Reset key and the ASCII command
vi
BE1-851 Introduction